This calculator works out air changes per hour (ACPH) for a cleanroom or any ventilated room. It first calculates the supply airflow in CFM (or m³/h) from the number of filters, their face area and the measured face velocity, then divides the hourly airflow by the room volume. Capture-hood readings or a known total airflow can be entered instead.
How many air changes per hour does a cleanroom need?
No ISO 14644 standard sets a required air change rate for a cleanroom class. The class is defined by particle concentration, and the air change rate is a design value chosen so that the room reaches that class and recovers quickly enough. The table compares the figures that are published in guidance documents with the ranges commonly quoted in the industry.
| ISO class (former FS 209E class) | Commonly quoted ACPH range | USP <1116> | FDA aseptic processing guidance (2004) | ISPE HVAC Good Practice Guide |
|---|---|---|---|---|
| ISO 5 (Class 100) | 240–480 | More than 100 | Significantly higher than 20; no figure given | No figure |
| ISO 6 (Class 1,000) | 150–240 | No figure | Significantly higher than 20; no figure given | No figure |
| ISO 7 (Class 10,000) | 60–90 | More than 50 | Significantly higher than 20; no figure given | 40–60 (EU Grade B) |
| ISO 8 (Class 100,000) | 5–48 | Minimum of 20 | At least 20 is typically acceptable | 20–40 (EU Grade C) |
- USP <1116>: describes these as typical design values and states that they should be used only as a guide, because the relationship between air changes, air velocity and microbial control has not been established experimentally. It also notes that airflow visualisation (smoke studies) is probably more useful than absolute velocity or air change figures.
- EU GMP Annex 1: gives no minimum air change rate. It uses a clean-up (recovery) period with a guidance value of 15–20 minutes.
- WHO: recommends 6–20 air changes per hour for non-sterile manufacturing and gives no figure for sterile operations.
- ISO 5 areas: are normally unidirectional airflow zones controlled by air velocity, so an air change rate is rarely specified for them.
- Current practice: ISO 14644-16 and the revised ISPE guidance favour calculating the air change rate from the expected particle load and recovery time instead of using a fixed figure.
For the particle limits behind each class, see ISO 14644-1 cleanroom classification and cleanroom grades A, B, C and D vs ISO classes. The number of particle sampling points is covered by the ISO 14644-1 sampling location calculator.
How to use the ACPH calculator
- Choose imperial (ft, in, fpm, CFM) or metric (m, mm, m/s, m³/h) units.
- Enter the room length, width and height. The room volume is shown underneath.
- Choose how the airflow was measured: five velocity readings on each filter, an average face velocity per filter group, airflow per filter with a capture hood, or a known total.
- Choose whether the filter size is entered in inches or feet (millimetres or metres in metric).
- For five-point readings, add one row per filter and enter the filter face length and width and the velocity at the four corners and the centre. The calculator averages the readings and multiplies by the face area to give the CFM of that filter.
- For an average face velocity, enter the number of filters, the filter face length and width, and the average velocity. Add a group for each different filter size or velocity.
CFM and ACPH formulas
| Step | Imperial | Metric |
|---|---|---|
| Step 1: Average face velocity | Average (fpm) = sum of the readings ÷ number of readings | Average (m/s) = sum of the readings ÷ number of readings |
| Step 2: Filter face area | Area (ft²) = length (ft) × width (ft). In inches: length × width ÷ 144 | Area (m²) = length (m) × width (m). In millimetres: length × width ÷ 1,000,000 |
| Step 3: Airflow per filter | CFM = average face velocity (fpm) × area (ft²) | m³/h = average face velocity (m/s) × area (m²) × 3,600 |
| Step 4: Total supply airflow | Sum of CFM for all filters | Sum of m³/h for all filters |
| Step 5: Room volume | ft³ = length × width × height (ft) | m³ = length × width × height (m) |
| Step 6: Air changes per hour | ACPH = total CFM × 60 ÷ room volume (ft³) | ACPH = total m³/h ÷ room volume (m³) |
Worked example
A room is 20 ft × 15 ft × 10 ft, so its volume is 3,000 ft³. It has four 24 in × 48 in terminal HEPA filters, each with a face area of 24 × 48 ÷ 144 = 8 ft². The average face velocity is 90 fpm, so each filter supplies 90 × 8 = 720 CFM and the four together supply 2,880 CFM. ACPH = 2,880 × 60 ÷ 3,000 = 57.6 air changes per hour.
With five-point readings on a single filter: velocities of 240, 280, 200, 250 and 230 fpm average 240 fpm. On a 2.5 ft × 2 ft filter (5 ft²) that is 240 × 5 = 1,200 CFM. In a 10 ft × 10 ft × 12 ft room (1,200 ft³), ACPH = 1,200 × 60 ÷ 1,200 = 60 air changes per hour.
How the airflow is measured
ISO 14644-3:2019 describes the airflow test in Annex B.2. For non-unidirectional (turbulent) cleanrooms, the supply air volume flow rate is either measured directly with a capture hood placed over each terminal filter or diffuser, or calculated from velocity readings taken across the filter face. For unidirectional airflow, the supply volume is calculated from the velocity measurements. The air change rate is then the total supply volume per hour divided by the room volume.
- Capture hood: gives the airflow of each filter directly and is generally preferred for non-unidirectional rooms.
- Face velocity: take several evenly spaced readings across each filter, average them, and multiply by the effective filter face area (the media area, not the outer frame).
- Room volume: use the internal dimensions of the room. Sites differ on whether large fixed equipment is subtracted; follow the approved qualification protocol.
Frequently Asked Questions (FAQs)
What is ACPH?
ACPH means air changes per hour: the number of times in one hour that a volume of air equal to the room volume is supplied to the room. It is also written ACH or air change rate (ACR).
How do you calculate CFM from filter face velocity?
Multiply the average face velocity in feet per minute by the filter face area in square feet. A 24 in × 48 in filter (8 ft²) at 90 fpm delivers 720 CFM.
How do you convert CFM to ACPH?
Multiply the total CFM by 60 to get cubic feet per hour, then divide by the room volume in cubic feet.
How do you convert CFM to m³/h?
Multiply CFM by 1.699. To convert m³/h to CFM, multiply by 0.5886.
Should one calculator be used for supply and return air?
Air changes are calculated from the supply air delivered to the room. Return or exhaust airflow is measured to check the room balance and pressure, not to calculate ACPH.
Does a higher ACPH always mean a cleaner room?
No. Airflow pattern, filter coverage, the position of returns, the number of people and the process all affect cleanliness. The air change rate is one design parameter and the result is verified by particle counts and recovery testing.
References
- ISO 14644-3:2019. Cleanrooms and associated controlled environments. Part 3: Test methods. Annex B.2, Airflow test.
- U.S. Food and Drug Administration. Guidance for Industry: Sterile Drug Products Produced by Aseptic Processing, Current Good Manufacturing Practice. 2004.
- ISO 14644-4:2022. Cleanrooms and associated controlled environments. Part 4: Design, construction and start-up.
- European Commission. EU GMP Annex 1: Manufacture of Sterile Medicinal Products. 2022.
- United States Pharmacopeia. General Chapter <1116> Microbiological Control and Monitoring of Aseptic Processing Environments.
- ISPE. Pharmaceutical Cleanroom Design and ISO 14644-16. Pharmaceutical Engineering, September/October 2021 (summarises the ISPE Good Practice Guide: Heating, Ventilation, and Air Conditioning, FDA, EU GMP and WHO figures). ispe.org
- Terra Universal. FS209E and ISO Cleanroom Standards (source of the commonly quoted air change ranges). terrauniversal.com
This calculator is a working aid. For qualification and release decisions, follow the approved protocol, calibrated instrument readings and site procedures.